Customization: | Available |
---|---|
Media: | Oil |
Temperature: | Low Temperature |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Veson valve ltd. ART series automatic recirculation valve is a kind of pump protection device. It automatic protect centrifugal pump when pump body occur cavitation damage or unstable (especially conveying hot water at low load operation medium). Once pump flow is lower than the preseted flow, bypass can completely open to ensure the minimum required flow pump. Even running fully closed, namely running flow is zero, the minimum flow can also pass bypass for Automatic Recycle. Pressure reduced through the multistage bypass pressure reducing valve.
ART series has big bypass, and this valve is suitable for bypass with big flow, maximum pressure differential is 4MPa, specific choice is determined by factory.
Body material Sealing material |
WCB | LCB/LCC | CF8 | CF8M |
NBR | -20~+100 | -30~+100 | -30~+100 | -30~+100 |
FKM | -20~+200 | -40~+200 | -40~+200 | -40~+200 |
PTFE | -20~+230 | -40~+230 | -80~+230 | -80~+230 |
SS winding gasket | -20~+300 | -40~+300 | -196~+300 | -196~+300 |
AR | T | Nominal pressure | Body material | Main diameter |
/Bypass diameter | Structure type |
Auto recirculation pump protection valve | T type bypass assembly | PN16=PN16 CLSS150LB=CL150 |
C=WCB LC=LCB P=CF8 PL=CF3 R=CF8M RL=CF3M D=Customed |
DN25=25 NPS1″=1″ |
DN25=25 NPS1″=1″ |
V=vertically mounted H=Horizontally mounted Z=Bypass non-return D=With discharge mouth |
Such as: T type automatic recirculation valve, pressure is PN40, body material is WCB, main diameter DN50, Bypass diameter DN 25, vertically mounted, Model: ART-PN40-C-50/25-V |
According to the difference of inductive main flow, main valve disc check cone of automatic recirculation valve will automatically move to a certain position. At the same time the main valve disc drive bypass valve stem, transfer the movement of main valve disc to bypass, through control bypass valve disc position, change bypass throttling area, so as to control bypass flow. When main valve disc back into valve seat closed, all flow backflow through bypass. When mian valve disc to rise to top position, bypass is fully closed, all the flow of pump flow to process system. This valve set four functions in one body.
Valve size | mm | 25 | 32 | 40 | 50 | 65 | 80 | 100 | 125 | 150 | 200 | 250 | 300 |
in | 1 | 11/4 | 11/2 | 2 | 21/2 | 3 | 4 | 5 | 6 | 8 | 10 | 12 | |
Max main flow | m3/h | 12 | 28 | 30 | 50 | 100 | 114 | 200 | 400 | 455 | 750 | 1250 | 1650 |
Bypass size | mm | 15 | 20 | 20 | 25 | 40 | 40 | 50 | 80 | 80 | 100 | 100 | 150 |
in | 1/2 | 3/4 | 3/4 | 1 | 11/2 | 11/2 | 2 | 3 | 3 | 4 | 4 | 6 | |
Max bypass Kv | Cv | 2.3 | 4.6 | 4.6 | 6.9 | 18.5 | 18.5 | 34.7 | 69.3 | 69.3 | 116 | 116 | 170 |
Note: Valve mian ouelet size depends on the outlet size of pump.
Valve specification DNP DNR |
Size mm(in) | Bypass | Weight Kg | |||
PN10/16/25 150lbs |
PN40/64 300lbs |
|||||
S | H | L | (DNB) | |||
25( 1″) | 115 | 102 | 267 | 15 | 12 | 18 |
32( 11/4″) | 115 | 102 | 267 | 20 | 14 | 20 |
40( 11/2″) | 115 | 102 | 267 | 20 | 14 | 20 |
50( 2″) | 130 | 108 | 305 | 25 | 22 | 26 |
65( 21/2″) | 165 | 127 | 381 | 40 | 46 | 51 |
80( 3″) | 181 | 127 | 381 | 40 | 46 | 51 |
100( 4″) | 209 | 159 | 495 | 50 | 105 | 118 |
125( 5″) | 267 | 220 | 575 | 80 | 143 | 156 |
150( 6″) | 267 | 220 | 575 | 80 | 220 | 240 |
200( 8″) | 300 | 220 | 600 | 100 | 255 | 302 |
250( 10″) | 356 | 305 | 780 | 100 | 400 | 455 |
300( 12″) | 530 | 280 | 830 | 150 | 590 | 650 |
Since product innovation and technical innovation or some special requirements, various valve connecting size may change, please contact Datian Valve technical department to get the latest product information.